REACTIVE POWER CAPACITOR UNITS WITH AUTOMATIC CONTROL

Operating principle of  high-voltage capacitor units  All high-voltage capacitor units, regardless of type, are designed to compensate ballast reactive power in the internal power supply system of the enterprise.  This reduces the need for power production at power plants and transmission over the network, increasing the capacity of the lines for active power. In addition, the high voltage capacitor units allow for optimizing the voltage in the internal networks of the enterprise during periods of maximum and minimum loads. Units with automatic power control also avoid overcompensation - excessive generation of reactive power and transmission to the supply network.
Ask about the product

Description

Construction and operational features.  Selection criteria

From the constructive point of view, each reactive power capacitor unit is a set of capacitor cells (controlled and non-controlled type) and input cells. Inside the cells, which are accessed from the front end of the structure, there is a control circuit for the main and auxiliary circuits.  The number of cells depends on the power of the units and the number of control steps.

Unlike the non-controlled capacitor units, the controlled capacitors have not only fuses and three-phase capacitors, but also vacuum contactors, as well as shunt reactors. Each fuse is equipped with a trigger indicator which is monitored through the view port.  In addition, the capacitors are completed with the discharge resistors.

The door of the input cell is equipped with a power controller, lighting, ammeters.

Purpose. Scope

The reactive power capacitor units are used to increase the reactive power factor of electrical systems of industrial facilities with a voltage of 6 – 10 kV.  Due to the technical and operational parameters of the units, the power factor at minimum and maximum network loads is maintained automatically and the possibility of overcompensation is absolutely excluded.

The units establish a clear balance of reactive power independently, and do not require the intervention of the maintenance personnel. The use of capacitor units reduces the current load on all distribution equipment, normalizes the voltage in load centers of the power system.  These devices are reasonable to be purchased if the company intends to optimize the operation of its power system.  Such products are necessary for the majority of industrial facilities of engineering, oil, gas, and food complex, as well as at any enterprises dealing with large volumes of consumed electricity.

Part type designation Unit power, kVAr Fixed part power, kVAr Control step, kVAr Overall dimensions, mm* Weight, kg, not to exceed* Regulations
length width height
УКРМ56(57)-6,3(10,5)
-450-(2×225) У3
450  

 

225 2770 825 1830 960 СТ 1474- 1917-АО-4-027-2012
and according to agreed technical assignment
УКРМ56(57)-6,3(10,5)
-450-(3×150) У3
150 905
УКРМ56(57)-6,3(10,5)
-750-(5×150) У3
750 3670 1220
УКРМ56(57)-6,3(10,5)
-900-(4×225) У3
900 225 1240
УКРМ56(57)-6,3(10,5)
-900-(2×450) У3
450 2770 960
УКРМ56(57)-6,3(10,5)
-900-(3×300) У3
300 3470 1085
УКРМ56(57)-6,3(10,5)
-900-(450+2×225) У3
450 225 1120
УКРМ56(57)-6,3(10,5)
-900-(450+3×150) У3
150 1125
УКРМ56(57)-6,3(10,5)
-1125-(5×225) У3
1125 225 3670 1270
УКРМ56(57)-6,3(10,5)
-1350-(3×450) У3
1350 450 3470 1155
УКРМ56(57)-6,3(10,5)
-1350-(450+4×225) У3
450 225 4370 1455
УКРМ56(57)-6,3(10,5)
-1350-(450+2×450) У3
450 3470 1180
УКРМ56(57)-6,3(10,5)
-1350-(450+3×300) У3
300 4170 1305
УКРМ56(57)-6,3(10,5)
-1350-(900+2×225) У3
900 225 3470 1185
УКРМ56(57)-6,3(10,5)
-1350-(900+3×150) У3
150 1190
УКРМ56(57)-6,3(10,5)
-1500-(5×300) У3
1500 300 4370 1445
УКРМ56(57)-6,3(10,5)
-1800-(450+3×450) У3
1800 450 450 4170 1370
УКРМ56(57)-6,3(10,5)
-1800-(900+3×300) У3
900 300 1370
УКРМ56(57)-6,3(10,5)
-1800-(900+4×225) У3
225 4370 1525
УКРМ56(57)-6,3(10,5)
-1800-(900+2×450) У3
450 3470 1245
УКРМ56(57)-6,3(10,5)
-1800-(1350+2×225) У3
1350 225 4170 1405
УКРМ56(57)-6,3(10,5)
-1800-(1350+3×150) У3
150 1410
УКРМ56(57)-6,3(10,5)
-2250-(5×450) У3
2250 450 4370 1560
УКРМ56(57)-6,3(10,5)
-2250-(900+3×450) У3
900 4170 1440
УКРМ56(57)-6,3(10,5)
-2250-(1350+4×225) У3
1350 225 5070 1745
УКРМ56(57)-6,3(10,5)
-2250-(1350+2×450) У3
450 4170 1465
УКРМ56(57)-6,3(10,5)
-2250-(1350+3×300) У3
300 4870 1520
УКРМ56(57)-6,3(10,5)
-2250-(1800+2×225) У3
1800 225 4170 1475
УКРМ56(57)-6,3(10,5)
-2250-(1800+3×150) У3
150 1475
УКРМ56(57)-6,3(10,5)
-2700-(1350+3×450) У3
2700 1350 450 4870 1660
УКРМ56(57)-6,3(10,5)
-2700-(1800+2×450) У3
1800 4170 1535
УКРМ56(57)-6,3(10,5)
-2700-(1800+4×225) У3
225 5070 1810
УКРМ56(57)-6,3(10,5)
-2700-(1800+3×300) У3
300 4870 1655
УКРМ56(57)-6,3(10,5)
-2700-(2250+2×225) У3
2250 225 1690
УКРМ56(57)-6,3(10,5)
-2700-(2250+3×150) У3
150 1695
УКРМ56(57)-6,3(10,5)
-3150-(1800+3×450) У3
3150 1800 450 1725
УКРМ56(57)-6,3(10,5)
-3150-(2250+2×450) У3
2250 1750
УКРМ56(57)-6,3(10,5)
-3150-(2700+2×225) У3
2700 225 1760
УКРМ56(57)-6,3(10,5)
-3150-(2700+3×150) У3
150 1765
УКРМ56(57)-6,3(10,5)
-3600-(2700+2×450) У3
3600 450 1820

* On customer’s demand, it is possible to manufacture the units with the requirements different from those listed in the table.

Principle of the controlled capacitor units designation:

УКРМ УКРМ — capacitor unit;
ХХ- 56- — disconnect switch at the bushing: 56- with disconnect switch, 57- without disconnect switch;
ХХ- 10.5- — rated voltage, kV;
ХХХ- 3150- — rated power, kVAr;
(ХХХ+ (2700+ — fixed part, kVAr;
3х150) 3х150) — number x power of compensation stages, pcs x kVAr, kVAr;
Х У — climatic version according to GOST 15150-69;
Х 3 — placement category according to GOST 15150-69;

Advantages. Economic effect

The reactive power capacitor units provide autonomous retention of the programmed power factor (due to the timely disconnection or switching of the control stages), overload protection, alarms, protection against distortions of higher harmonics, indication of the current in capacitor banks.  Operation in manual mode implies the possibility manually to switch off and connect the control stages.

Due to efficient operation of the capacitors with manual and automatic power control in the area of RPC (reactive power compensation), their use at industrial enterprises and facilities greatly benefits economy.

 

  • The power factor significantly increases that virtually excludes the potential for penalties imposed on the company by the representatives of power supply companies.
  • The useful active power losses are reduced in the electricity distribution and transmission.
  • The voltage losses are reduced in the electricity distribution and transmission.
  • It is possible to connect additional capacity without rising the cost of the power system by increasing the capacity of the feeders.
  • The financial costs for electricity production and consumption are cut down, the system as a whole starts operating more reliably and cost-effectively.

 